TROX TVT – Rectangular VAV Terminal for Normal & High Flow Rates with Low Leakage Shut-Off

Call for Price

For normal and high volume flow rate ranges and lowleakage shut-off

Rectangular air terminal units for standard applications in supply air or extract air systems with variable volume flow rates, suitable for low-leakage shut-off

  • For volume flow rate ranges up to 16976 cfm
  • Suitable for the control of volume flow rate, room pressure or duct pressure
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • High control accuracy
  • Closed blade air leakage to EN 1751, class 3
  • Casing air leakage to EN 1751, up to class COptional equipment and accessories
  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TX for the reduction of air-regenerated noise
  • Hot water heat exchanger of Type WT for reheating the airflow
SKU: TVT Category: Tag:

General Information

Application
  • Rectangular VAV terminal units for use in ventilation and air conditioning systems
  • For controlling, restricting, or shutting off supply and extract air flows
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by means of switching (equipment supplied by others)
  • Can also be used for duct or room pressure control with suitable control components

 

Special characteristics
  • Integral effective pressure sensor with 0.1 in measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component.
  • Depending on the control component, an additional adjustment device may be necessary

 

Nominal sizes
  • 36 nominal sizes from 8 × 4 in to 40 × 24 in
  • Not all attachments may be available or suitable for all sizes of terminal units

 

Variants
  • TVT: VAV terminal unit
  • TVT-D: VAV terminal unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TX for demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted

 

Construction
  • Galvanised sheet steel
  • P1: Powder-coated, silver (RAL 7001)

 

Parts and characteristics
  • Ready-to-commission unit which consists of mechanical parts and control components
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blades
  • Factory assembled control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig before shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High volume flow rate control accuracy

 

Attachments
  • EASY controller: compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controller: controller, effective pressure transducer, and actuators for special applications
  • LABCONTROL: Control components for air management systems

 

Useful additions
  • Secondary silencer Type TX for demanding acoustic requirements
  • Heat exchanger Type WT

 

Construction features
  • Rectangular casing
  • Flanges on both ends, suitable for duct connection
  • Opposed blade action, blades connected by internal gears (enclosed) at both ends
  • Damper blades with replaceable seals
  • Position of the damper blade indicated externally at shaft extension
  • Bearings with ring seals

 

Material and surfaces
Galvanised sheet steel construction
  • Casing made of galvanised sheet steel
  • Shaft and linkage made of galvanised steel
  • Damper blades and effective pressure sensor made of aluminium
  • Gears made of anti-static plastic (ABS), temperature resistant to 122 °F
  • Plastic plain bearings
Powder-coated construction (P1)
  • Casing made of galvanised sheet steel, powder-coated
Variant with acoustic cladding (D)
  • Acoustic cladding made of galvanised sheet steel
  • Rubber seal for the insulation of structure-borne noise
  • Lining is mineral wool
Mineral wool
  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008

 

Standards and guidelines
Fulfils the hygiene requirements of
  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • For other applicable standards and guidelines refer to the hygiene certificate
Casing leakage
  • EN 1751, Class C; if B + H ≤ 16 in, Class B
Closed blade air leakage
  • EN 1751, Class 3
  • Meets the general requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

 

Maintenance

  • Maintenance-free as construction and materials are not subject to wear

Disclosure of Chemicals

RoHS EU Directive 2011/65/EU (RoHS)This product or single variants comply with EU Directive 2011/65/EU (RoHS) on the restriction of the use of certain hazardous substances in electrical and electronic equipment. For more information, please refer to our Environmental Product Declarations.

REACH 1907/2006 (EC Regulation REACH)This product or single variants comply with the provisions of EC Regulation No. 1907/2006, also known as REACH (Registration, Evaluation, Authorisation and Restriction of Chemicals). For more information, please refer to our Environmental Product Declarations.

Function

The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate. The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL). For most applications, the setpoint value comes from a room temperature controller. The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

 

Schematic Illustration of the TVT

① Effective pressure sensor
② Damper blade with seal
③ Gears
④ Control components, e.g. an Easy controller

Specification Text

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Specification text
Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in 36 nominal sizes. High volume flow rate control accuracy.
Ready-to-commission unit which consists of the mechanical parts and the electronic control components Each unit contains an averaging effective pressure sensor for volume flow rate measurement and damper blades. Factory mounted control components complete with wiring and tubing Effective pressure sensor with 0.1 in measuring holes, hence resistant to contamination. Position of the damper blades indicated externally at the shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed).
Special features
  • Integral effective pressure sensor with 0.1 in measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component.
  • Depending on the control component, an additional adjustment device may be necessary

 

Materials and surfaces
  • Casing made of galvanised sheet steel
  • Shaft and linkage made of galvanised steel
  • Damper blades and differential pressure sensor made of aluminium
  • Gears made of anti-static plastic (ABS), resistant to temperatures up to 122 °F
  • Plastic plain bearings

 

Connection type
  • Flanges on both ends, suitable for duct connection

 

Technical data
  • Nominal sizes: 8 × 4 in to 40 × 24 in
  • Volume flow rate range: 88 – 12454 cfm
  • Minimum differential pressure: up to 0.42 in WG
  • Maximum differential pressure: 4.01 in WG
  • Closed blade air leakage to EN 1751, class 3
  • Casing air leakage to EN 1751, class C (B + H ≤ 16 in, class B)

 

Equivalence criteria
  • Declaration of hygiene conformity according to VDI 6022, sheet 1 (01/2018), ÖNORM H 6020 (02/2007) and ÖNORM H 6021 (09/2003)
  • Fulfils the hygiene requirements according to EN 16798 Part 3, VDI 6022 Sheet 1, DIN 1946 Part 4.
  • Acoustic data determined in accordance with ÖNORM EN ISO 5135:1999
  • Setting the volume flow rates without a setting device via qvmin and qvmax potentiometers
  • Electrical connections with screw terminals, no additional terminal boxes required
  • Each volumetric flow controller is factory-tested on an air test bench and certified with a sticker on the controller

 

Specification text attachment

Variable volume flow control with electronic Easy controller for applying a reference value and capturing an actual value to be integrated with the central BMS.

  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using voltfree contacts: CLOSE, OPEN, qᵥmin and qᵥmax without adjustment device
  • Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax without adjustment device
  • The actual value signal relates to the nominal volume flow rate so that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 20 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
  • Electrical connections with screw terminals
  • Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller

 

Life cycle assessment
A life cycle assessment is available for the product type in the form of an environmental product declaration (EPD), which has been checked and published by a programme holder.

Downloads

TVT Product Data Sheet

TVT, TVJ Declaration of Conformity or Declaration of Incorporation

TVT Declaration of Hygiene Conformity

TVT Environmental Product Declaration

TVT-D Environmental Product Declaration

TVT Manufacturer’s Statement Concerning Statistical Leakage

Replacing GUAC Actuators Installation Instructions