TROX LON-WA TDC – Control Deivces

Call for Price

For the temperature-based control of adjustable air terminal devices, for heating or cooling mode

Ideal adjustment of the discharge angle to varying loads

  • For adjustable air terminal devices
  • Heating, cooling, isothermal operation
  • Adjustment of the discharge direction based on the supply air to room air temperature
  • Bespoke solutions, adjustment of the characteristic
  • For up to 20 heating/cooling actuators (3-point)
  • For up to 10 modulating rotary actuators or 5 modulating spindle actuators
  • Override controls
SKU: LON-WA TDC Category: Tag:

Application

Application

  • Type LON-WA TDC control modules for the temperature-based control of adjustable air terminal devices, for heating or cooling mode
  • For air terminal devices Types VD, VDL, VDR, QSH, ISH, TJN, DUK and DG-VAR
  • Heating, cooling, isothermal operation
  • Analogue output for modulating actuators
  • Digital output for 3-point actuators
  • LonWorks interface for the transmission of standard network variables
  • A plug-in for all LNS-based network integration tools (LNS version 3.3 and higher) is available for configuration

Special characteristics

  • Bespoke solutions since the characteristic can be adjusted
  • Temperature values are transmitted as voltage signals or network variables
  • Control input for actuators with a modulating signal (0 – 10 V DC) or 3-point (24 V AC)
  • Override control functions for heating up, variable operation, heating, cooling and isothermal operation

Description

Parts and characteristics

  • Microprocessor system with programme and system data stored in nonvolatile memory
  • Double-stack terminal block for supply voltage connection and communication cable
  • Inputs and outputs with screw terminals

Construction features

  • PCB with terminals enclosed in a casing
  • Casing is to be screw-fixed to the installation surface
  • Casing with knockouts for cables

Materials and surfaces

  • Plastic casing

Maintenance

  • Maintenance-free as construction and materials are not subject to wear

Function

Functional description

Adjustable air terminal devices with actuators are used to achieve the best possible air distribution in high and large rooms with changing thermal loads. Type LON-WA TDC control modules control actuators based on the supply air to room air difference.

Supply air temperature and room air temperature are measured with external sensors and transmitted as voltage signals or LonWorks network variables Characteristic curve values translate into discharge angles, and the actuators are set accordingly.

Override functions are available to set various operating modes.

The program sequence of the control module includes a watchdog and a heartbeat function to monitor and maintain operation.

Operating modes

Temperature difference control

  • Calculation of the supply air to room air temperature difference
  • Discharge angle corresponds to characteristic
  • Standard operating mode if temperature difference control has been configured
  • No override functions

Variable operation

  • Direct control of the discharge angle with a voltage signal (AI1) or with a network variable (nviManCntrl)
  • Temperature difference is neglected
  • Standard operating mode if variable operation has been configured
  • No override functions

Cooling

  • Override function, the discharge angle is reduced to the minimum
  • Minimum angle is defined with SCPTminRnge (nvoActuatorPos)
  • Set via DI1 or nviDI1_State

Isothermal operation

  • Override function, the discharge angle is neutral
  • Neutral position is defined with SCPTdischargeAirHeatingSetpoint
  • Set via DI2 or nviDI2_State

Heating

  • Override function, the discharge angle is increased to the maximum
  • The maximum angle is defined with SCPTmaxRnge (nvoActuatorPos) and SCPTdischargeAitCoolingSetpoint
  • Set via DI3 or nviDI3_State

Heating up

  • Override function, the discharge angle is reduced to the minimum
  • Set via DI4 or nviDI4_State

Inputs

Two analogue inputs

  • Analogue inputs with configurable characteristic for signalling the supply air temperature and the room air temperature
  • With variable operation: Analogue input for signalling the setpoint discharge angle

Four digital inputs

  • Digital inputs for volt-free switches
  • Override functions for variable operation, cooling, heating and isothermal operation

Outputs

One analogue output

  • Analogue output with configurable characteristic for signalling to modulating actuators

Two digital outputs

  • Digital outputs for signalling to heating/cooling actuators, 2-wire control (3-point)

Interface to the central BMS

  • Actual operating values and fault messages of the control module are transferred via the network
  • Supply air temperature, room air temperature, discharge angle
  • Status of the digital inputs and voltage at each analogue input

 

LON-WA TDC Temperature Difference Control for Adjustable Air Terminal Devices with an Actuator

① LON-WA TDC control module
② Room temperature sensor, by others
③ Supply air temperature sensor, by others
④ Actuator, attached to the air terminal device

Specification Text

Control modules for signalling the temperature-based control input signal to adjustable air terminal devices with an actuator. For the connection of external temperature sensors for supply air and room air. A project-specific characteristic with two operating points to define the discharge angle based on the supply air to room air temperature difference is stored in the control module and cannot be deleted.

Ready-to-operate unit which consists of a PCB and a casing with knockouts. Control module electronics using a microprocessor, with configuration settings stored in EEPROM memory and hence safe in case of a power failure. Two analogue inputs, four volt-free digital inputs, one analogue output and two digital outputs as relay contacts.

The control modules include a LonWorks transceiver FTT-10A (free topology, twisted pair) and a service pin for LonWorks integration.

For the connection of modulating actuators to the analogue output, or of heating/cooling actuators (3-point) to the digital output.

Special characteristics

  • Bespoke solutions since the characteristic can be adjusted
  • Temperature values are transmitted as voltage signals or network variables
  • Control input for actuators with a modulating signal (0 – 10 V DC) or 3-point (24 V AC)
  • Override control functions for heating up, variable operation, heating, cooling and isothermal operation

Materials and surfaces

  • Plastic casing

Technical data

  • Supply voltage: 24 V AC ±15 %, 50/60 Hz
  • Power rating: 3.5 VA
  • Communication interface: LonWorks transceiver FTT-10A (free topology, twisted pair)
  • Connection of LonWorks network: 4 terminals for cables with a cross section between 0.00012 and 0.00388 in², with reverse polarity protection
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 65