Description
COMPACT VAV SOLUTION FOR LOW AIRFLOW VELOCITIES
Circular air terminal units for variable air volume systems with low airflow velocities, suitable even with unfavorable upstream conditions
- Effective pressure measurement not with a tube, but by means of the damper blade
- Effective pressure transmission through effective pressure channel in the shaft
- Terminals with protective cover – no junction box required
- Any airflow direction if dynamic transducer is used
- Suitable for airflow velocities of 100 – 2550 ft/min
- Compact dimensions allow for use in restricted spaces
- Plug-and-play solution in conjunction with X-AIRCONTROL room control
- Exact measurement even with low airflow velocities
- Any installation orientation even with static transducer
- Closed blade air leakage to EN 1751, at least class 3
- Casing air leakage to EN 1751, class C
- Volume flow rate range 1:25
Optional equipment and accessories
- Acoustic cladding for the reduction of case-radiated noise
- Secondary silencer CA (for Germany and Switzerland), CAH (for EMEA) or CF, for the reduction of air-regenerated noise
- Hot water heat exchanger WL and electric air heater EL for reheating the airflow
Application
- Circular VAV terminal units for use in ventilation and air conditioning systems
- For virtually all control, inductor and shut-off tasks in the supply air or extract air area
- Also for unfavorable upstream conditions at low airflow velocities
- Closed-loop volume flow control using an external power supply
- For variable or constant volume flow systems
- Shut-off via override control by others
Special features
- High effective pressure signal at a small angle of attack
- Factory set-up or programming and aerodynamic function testing
- Volume flow rate can be measured and subsequently adjusted on site; additional adjustment tool may be necessary (depending on the variant of the control component)
- Effective pressure monitoring tubeless via damper blade
- Effective pressure transmission through effective pressure channel in shaft
- Any direction of flow with dynamic transducer
- Any installation orientation, even with static transducers
- Suitable for airflow velocity of 100 – 2550 ft/min
- Compact dimensions for use in confined ceiling areas
Nominal Sizes
- 4″, 5″, 6″, 8″, 10″, 12″, 16″
Variants
- TVE: VAV terminal unit
- TVE-D: VAV terminal unit with acoustic cladding
- TVE-FL: VAV terminal unit with flanges on both ends
- TVE-D-FL: VAV terminal unit with acoustic cladding and flanges on both ends
- Units with acoustic cladding and/or a secondary silencer CA (for Germany and Switzerland), CH (for EMEA) or CF for demanding acoustic requirements
Construction
- Galvanized sheet steel
Parts and characteristics
- Ready-to-commission unit which consists of mechanical parts and control components.
- Damper blade with integrated measuring unit
- Shaft with effective pressure channel for measured value transmission
- Factory-assembled control components complete with wiring
- Aerodynamic functional testing on a special test rig prior to shipping of each unit
- Set-up data is given on a label or volume flow rate scale affixed to the unit
- High control accuracy, even in unfavorable upstream conditions
Attachments
- EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
Accessories
- D2: Double lip seals on both ends (factory fitted)
Useful additions
- Secondary silencer CA (for Germany and Switzerland), CAH (for EMEA) or CF
- Heat exchanger WL
- Electric air heater EL
Construction features
- Circular casing
- Spigot suitable for circular ducts to EN 1506 or EN 13180
- Spigots with groove for seal
- Position of the damper blade indicated externally at position indicator
- Control component can be replaced
Materials and surfaces
Galvanized sheet steel
- Casing made of galvanized sheet steel
- Damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
- Damper blade seal made of plastic, TPU, antimicrobial
- Plastic plain bearings
Mineral wool
- To EN 13501, fire rating Class A1, non-combustible
- RAL quality mark RAL-GZ 388
- Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
Standards and guidelines
Fulfils the hygiene requirements of
- EN 16798, Part 3
- VDI 6022, Sheet 1
- DIN 1946, Part 4
- For other applicable standards and guidelines refer to the hygiene certificate
Casing leakage
- EN 1751, Class C
Closed blade air leakage:
NS 100 – 160
- EN 1751, Class 3
- Meets the general requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage
NS 200 – 400
- EN 1751, Class 4
- Meets the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage
Maintenance
- Maintenance-free as construction and materials are not subject to wear
Literature
- Product Brochure
- Product IOM
- TVE Sales Flyer
- Installation and commissioning instructions Easy Controller