FOR VARIOUS STANDARD APPLICATIONS

  • Circular air terminal units for standard applications in supply air or extract air systems with variable volume flow rates
  • Suitable for the control of volume flow rate, room pressure or duct pressure
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • High control accuracy even with upstream bend (R = 1D)
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, class C

Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer CA (for Germany and Switzerland), CAH (for EMEA) CS or CF for the reduction of air-regenerated noise
  • Hot water heat exchanger WL and electric air heater EL for reheating the airflow

Application

  • Circular VAV terminal units for use in ventilation and air conditioning systems
  • For controlling, restricting, or shutting off supply and extract air flows
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by means of switching (by others)
  • Can also be used for duct or room pressure control with suitable control components

Special features

  • Integral effective pressure sensor with 3 mm measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component; additional adjustment device may be necessary

Nominal sizes

  • 100, 125, 160, 200, 250, 315, 400

Variants

  • TVR: VAV terminal unit
  • TVR-D: VAV terminal unit with acoustic cladding
  • TVR-FL: VAV terminal unit with flanges on both ends
  • TVR-D-FL: VAV terminal unit with acoustic cladding and flanges on both ends
  • Units with acoustic cladding and/or a circular silencer CA (for Germany and Switzerland), CH (for EMEA), CS or CF for demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted

Construction

  • Galvanized sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)
  • A2: Stainless steel

Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blade
  • Factory assembled control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig before shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy (even with upstream bend R = 1D)

Attachments

  • EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controller: Controller, effective pressure transducer and actuators for special applications
  • LABCONTROL: Control components for air management systems

Accessories

  • G2: Matching flanges for both ends
  • D2: Double lip seals on both ends (factory fitted)

Useful additions

  • Circular silencer CA (for Germany and Switzerland), CH (for EMEA), CS or CF for demanding acoustic requirements
  • Heat exchanger WL
  • Electric air heater EL

Construction features

  • Circular casing
  • Spigot suitable for circular ducts to EN 1506 or EN 13180
  • Spigots with groove for seal
  • Position of the damper blade indicated externally at shaft extension
  • TVR-FL: Flanges to EN 12220

Materials and surfaces

Galvanized sheet steel construction

  • Casing and damper blade made of galvanized sheet steel
  • Damper blade seal made of TPE plastic
  • Aluminum sensor tubes
  • Plastic plain bearings

Powder-coated construction (P1)

  • Casing made of galvanized sheet steel, powder-coated
  • Damper blade and shaft made of stainless steel 1.4301
  • Sensor tubes made of aluminum, powder-coated

Stainless steel construction (A2)

  • Casing, damper blade and shaft made of stainless steel 1.4301
  • Sensor tubes made of aluminum, powder-coated

Variant with acoustic cladding (-D)

  • Acoustic cladding made of galvanized sheet steel
  • Rubber seal for the insulation of structure-borne noise
  • Lining is mineral wool

Mineral wool

  • To EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008

Standards and guidelines

Fulfils the hygiene requirements of

  •     EN 16798, Part 3
  •     VDI 6022, Sheet 1
  •     DIN 1946, Part 4
  •     For other applicable standards and guidelines refer to the hygiene certificate

Casing leakage

  • EN 1751, Class C

Closed blade air leakage:

NS 100

  • EN 1751, Class 2
  • Meets the general requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

NS 125 – 160

  • EN 1751, Class 3
  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed blade air leakage

NS > 160

  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed blade air leakage

Maintenance

  • Maintenance-free as construction and materials are not subject to wear