TROX TVE-160-D2-Easy – 6″ Circular Variable Air Volume Terminal for low airflow velocities, in unfavorable upstream conditions, with Easy Controller

Call for Price

E:Mail: [email protected] to confirm availability or for volume discounts

Description

COMPACT VAV SOLUTION FOR LOW AIRFLOW VELOCITIES

Circular air terminal units for variable air volume systems with low airflow velocities, suitable even with unfavorable upstream conditions

  • Effective pressure measurement not with a tube, but by means of the damper blade
  • Effective pressure transmission through effective pressure channel in the shaft
  • Terminals with protective cover – no junction box required
  • Any airflow direction if dynamic transducer is used
  • Suitable for airflow velocities of 100 – 2550 ft/min
  • Compact dimensions allow for use in restricted spaces
  • Plug-and-play solution in conjunction with X-AIRCONTROL room control
  • Exact measurement even with low airflow velocities
  • Any installation orientation even with static transducer
  • Closed blade air leakage to EN 1751, at least class 3
  • Casing air leakage to EN 1751, class C
  • Volume flow rate range 1:25

Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer CA (for Germany and Switzerland), CAH (for EMEA) or CF, for the reduction of air-regenerated noise
  • Hot water heat exchanger WL and electric air heater EL for reheating the airflow

Application

  • Circular VAV terminal units for use in ventilation and air conditioning systems
  • For virtually all control, inductor and shut-off tasks in the supply air or extract air area
  • Also for unfavorable upstream conditions at low airflow velocities
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off via override control by others

Special features

  • High effective pressure signal at a small angle of attack
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can be measured and subsequently adjusted on site; additional adjustment tool may be necessary (depending on the variant of the control component)
  • Effective pressure monitoring tubeless via damper blade
  • Effective pressure transmission through effective pressure channel in shaft
  • Any direction of flow with dynamic transducer
  • Any installation orientation, even with static transducers
  • Suitable for airflow velocity of 100 – 2550 ft/min
  • Compact dimensions for use in confined ceiling areas

Nominal Sizes

  • 4″, 5″, 6″, 8″, 10″, 12″, 16″

Variants

  • TVE: VAV terminal unit
  • TVE-D: VAV terminal unit with acoustic cladding
  • TVE-FL: VAV terminal unit with flanges on both ends
  • TVE-D-FL: VAV terminal unit with acoustic cladding and flanges on both ends
  • Units with acoustic cladding and/or a secondary silencer CA (for Germany and Switzerland), CH (for EMEA) or CF for demanding acoustic requirements

Construction

  • Galvanized sheet steel

Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Damper blade with integrated measuring unit
  • Shaft with effective pressure channel for measured value transmission
  • Factory-assembled control components complete with wiring
  • Aerodynamic functional testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy, even in unfavorable upstream conditions

Attachments

  • EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator

Accessories

  • D2: Double lip seals on both ends (factory fitted)

Useful additions

  • Secondary silencer CA (for Germany and Switzerland), CAH (for EMEA) or CF
  • Heat exchanger WL
  • Electric air heater EL

Construction features

  • Circular casing
  • Spigot suitable for circular ducts to EN 1506 or EN 13180
  • Spigots with groove for seal
  • Position of the damper blade indicated externally at position indicator
  • Control component can be replaced

Materials and surfaces

Galvanized sheet steel

  • Casing made of galvanized sheet steel
  • Damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, antimicrobial
  • Plastic plain bearings

Mineral wool

  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008

Standards and guidelines

Fulfils the hygiene requirements of

  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • For other applicable standards and guidelines refer to the hygiene certificate

Casing leakage

  • EN 1751, Class C

Closed blade air leakage:

NS 100 – 160

  • EN 1751, Class 3
  • Meets the general requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

NS 200 – 400

  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

Maintenance

  • Maintenance-free as construction and materials are not subject to wear

Literature