TROX MFP – Mini Pleat Panel Filter

Call for Price

FOR THE MOST DEMANDING REQUIREMENTS OF AIR CLEANLINESS AND STERILITY

SKU: MFP Category: Tag:

Description

Application

  • Mini Pleat filter panel for the separation of fine dust and suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply and extract air in ventilation systems with large volume flows and long filter lives
  • Fine dust filter: prefilter or final filter for the separation of fine dust in ventilation and air conditioning systems.
  • Particulate filter: main or final filter used for the most critical requirements of air cleanliness and sterility in areas such as industry, research, medicine, medicine, etc.

Special characteristics

  • Leakage test is standard for all particulate filters of classes H13, H14

Classification

  • Eurovent Certification for fine dust filters

Nominal sizes

B × H × D [mm]

Options

  • FT: pleat depth
  • PU: protection grid on the upstream side
  • PD: protection grid on the downstream side
  • PB: protection grid on both sides
  • FNU: flat profile seal on the upstream side
  • FND: flat profile seal on the downstream side
  • FNB: flat seal on both sides
  • TGU: test groove seal on the upstream side (only for filter classes H13, H14)
  • CSU: continuous seal on the upstream side
  • CSD: continuous seal on the downstream side
  • CSB: continuous seal on both sides
  • WS: without seal
  • OT: oil mist test (only for filter classes H13, H14)
  • OTC: oil mist test with certificate (only for filter classes H13, H14)
  • ST: filter scan test (only for filter classes H13, H14)

Construction

  • PLA: frame made of plastic (depth 48, 96, and 150 mm)
  • MDFF: frame made of MDF, with top frame (depth 60 mm)
  • MDF: frame made of MDF (depth 60, 78, 150, and 292 mm)
  • GAL: frame made of galvanized steel (depth 48, 60, 96, 150 and 292 mm)
  • STA: frame made of stainless steel (depth 48, 60, 96, 150 and 292 mm)
  • CBS cardboard frame, stapled (depth 45, 48, 90 and 96 mm)

Useful additions

  • Filter wall (SIF)
  • Universal casing (UCA)
  • Ducted particulate filter, available as one unit (KSF, KSFS) or as a filter unit system (KSFSSP)
  • Duct casing for particulate filters (DCA)
  • Ceiling mounted particulate filter (TFC)
  • Wall mounted particulate filter (TFW)
  • Particulate filter module (TFM)
  • Ceiling diffusers for extract air applications (TFEA)

Construction features

  • Circumferential flat seal on the upstream side for variants CBS, MDF, GAL, STA
  • Variants optionally with foamed continuous seal or with a test groove seal (filter classes H13, H14) on the upstream side
    • The flat seal or continuous seal can also be arranged on the downstream side or on both sides
  • Protection grid made of expanded metal: can be fitted on the downstream or upstream side or both sides as required

Materials and surfaces

  • Filter media made of high-quality, wet-strength glass fiber papers, pleated
  • Spacers provide a uniform spacing of the pleats
  • Joint sealing compound made of permanently elastic two component polyurethane adhesive
  • Frame optionally available in cardboard, plastic, fiberboard, galvanized sheet steel, stainless steel

Standards and guidelines

  • Tested according to ISO 16890; international standard for general ventilation and air conditioning; classification of fractional efficiency based on the measured fractional separation efficiency which is processed into a reporting system for the fine dust fractional efficiency (ePM)
  • For fine dust filters, the fractional separation efficiency of a certain size range is determined by aerosols (DEHS and KCl)
  • Depending on the test values, the filters are classified into filter groups ISO ePM10 and ISO ePM1
  • Testing of particulate filters according to EN 1822-1 and ISO 29463-2 to ISO 29463-5 (EPA, HEPA and ULPA particulate filters): standards for testing the filtration performance in the factory, based on particle counting methods using a liquid test aerosol.
  • Uniform classification of particulate filters according to separation efficiency, using a test aerosol with an average particle size within the minimum separation efficiency (MPPS)
  • Classification of particulate filters:
    • Determined local separation efficiency
    • Determined integral separation efficiency
  • Filter classes:
    • EPA: Filter classes: E10, E11, E12
    • HEPA: Filter classes: H13, H14

TECHNICAL INFORMATION

  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Fractional efficiency ePM10 [%] according to ISO 16890

55

Fractional efficiency ePM1 [%] according to ISO 16890

65

90

Initial differential pressure [Pa] at nominal volume flow rate

90

110

150

Final differential pressure [Pa]

450

450

450

Maximum operating temperature [°C]

80

80

80

Maximum relative humidity [%]

100

100

100

Filter class according to DIN EN 1822

E11

H13

H14

Separation efficiency [%] according to EN 1822

> 95

> 99.95

> 99.995

Initial differential pressure [Pa] at nominal volume flow rate

125

250

120/140

Final differential pressure [Pa]

300

600

300

Maximum operating temperature [°C]

80

80

80

Maximum relative humidity [%]

100

100

100

Order Code:

MFP H13 MDF / 610 × 610 × 78 × 50 / PD / FNU / ST
| | | | | | | | |
1 2 3 4 5 6 7 8 9

1 Type
MFP
 Mini Pleat filter panel

2 Filter class
ePM1 
Fractional efficiency ePM1 [%] according to ISO 16890
ePM10
Fractional efficiency ePM10 [%] according to ISO 16890
E11 
Filter class E11 according to EN 1822
H13
Filter class H13 according to EN 1822
H14 
Filter class H14 according to EN 1822

3 Separation efficiency

Only with filter class ePM1, ePM10
Specify separation efficiency [%] according to ISO 16890

4 Construction

CBS Cardboard frame, stapled

PLA Plastic frame

PLAF Frame made of plastic with flange (25 mm)

MDF Frame made of medium density fiberboard

MDFF Frame made of medium density fiberboard, with top frame

GAL Frame made of galvanized sheet steel

STA Frame made of stainless steel

5 Nominal size [mm]
Specify width × height × depth

6 Pleat depth [mm]
Specify pleat depth

7 Protection grid

No entry: without protection grid

PU Protection grid on the upstream side

PD Protection grid on the downstream side (with construction

ALN as standard)

PB Protection grid on both sides

8 Seal
WS without seal
FNU Flat seal on the upstream side
FND Flat seal on the downstream side
FNB  Flat seal on both sides
TGU  Test groove seal on the upstream side
CSU  Continuous seal on the upstream side
CSD  Continuous seal on the downstream side
CSB  Continuous seal on both sides

9 Testing
No entry: no leakage test
OT  Oil mist test (filter classes H13 and H14 only)
OTC  Oil mist test with certificate (filter classes H13 and H14 only)
ST Filter scan test (only with filter class H13, H14)

Order example: MFP-H13-MDF/610×610×78×50/PD/FNU/ST

Type MFP
Filter class Filter class H13 according to EN 1822
Separation efficiency
Construction Frame made of MDF
Nominal size ´[mm] Width 610, height 610, depth 78
Pleat depth [mm] 50
Protection grid Protection grid on the downstream side
Seal Flat seal on the upstream side
Testing scan test

Literature